§ 8-9-148 — Machine room or control room ventilation
2019 Detroit City Code (Supp. No. 4: codified through Ordinance No. 2024-17, effective March 26, 2024, and Ordinance No. 2024-32, effective June 25, 2024) · Detroit City Code § 8-9-148
Corpus is an independent public-information project, not the official City of Detroit website. Stable reference: corpuslaw.us/code/fbcaa510-d78f-4066-82d2-aa0f1b4585e9
Sec. 8-9-148. - Machine room or control room ventilation.
(a) Elevator machine rooms or control rooms, new or altered, shall be provided with an independent means of ventilation or air-conditioning to protect against the overheating of the electrical equipment. The system shall be capable of maintaining temperatures within the range established by the manufacturer's recommendation for the elevator equipment. (b) Where the elevator machine room is not equipped with an approved automatic sprinkler system, an approved smoke control system shall be provided in accordance with Chapter 8, Article II, of the 2019 Detroit City Code, Building Code, to vent smoke into the outer air in the case of fire. The aggregation capacity of smoke exhaust fans shall be determined by the following equation: Capacity Equals Area x 300 (C = A x 300).