§ 8-9-160 — Installation of sprinkler protections in hoistways, machinery spaces, machine rooms, or control rooms

2019 Detroit City Code (Supp. No. 4: codified through Ordinance No. 2024-17, effective March 26, 2024, and Ordinance No. 2024-32, effective June 25, 2024) · Detroit City Code § 8-9-160

Corpus is an independent public-information project, not the official City of Detroit website. Stable reference: corpuslaw.us/code/26f2ea07-434c-4acd-ad5c-f3fff7cd7b50

Sec. 8-9-160. - Installation of sprinkler protections in hoistways, machinery spaces, machine rooms, or control rooms.

(a) Sprinkler protection that conform to the requirements of the NFPA 13 may be installed in hoistways, machinery spaces, machine rooms or control rooms, subject to the following: (1) All risers and returns shall be located outside these spaces; (2) Branch lines in the hoistway shall supply sprinklers at not more than one floor; (3) Electronically supervised shut-off valves shall be provided in readily-accessible locations outside the hoistway, machine room or control room, provided, that, where an electronically pre-active sprinkler system, or similar type, is installed in accordance with NFPA 13, a shut-off valve is not required; and (4) Means shall be installed in the machine or control room to automatically disconnect the main-line power supply to the affected elevator prior to the application of water, but not until the elevator car has reached the designated landing and the car doors have opened and remain open, provided, that the means shall not be self-resetting and that the activation of sprinklers outside of the hoistway, machine room, or control room shall not disconnect the main-line power supply. (b) A separate fuse circuit breaker for heat sensors shall be installed in the elevator machine or control room and used for no other purpose. (c) An indicator light for the shunt trip operation shall be installed and located in the machine or control room for testing purposes. (d) Fire alarm initiating devices, or combination-type fire alarm initiating devices, shall not be used to activate shunt-trip operations in these spaces or to disconnect the main-line power supply. (e) Only rate-of-rise, fixed-temperature type fire alarm initiating devices are permitted in elevator pits, hoistways, machinery spaces, machine rooms, or control rooms.

Ask a question about Detroit law

Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.