Sec. 5-631. - International Residential Code—Section E3605.1 amended.

Section E3605.1 of the 2018 International Residential Code is hereby amended to read as follows: E3605.1 Insulation of service-entrance conductors. Service-entrance conductors entering or on the exterior of buildings or other structures shall be insulated in accordance with section E3406.5. Service-entrance conductors shall not exceed six feet in length from the point of entrance of a building. [230.41 Exception]. Exceptions: 1. A copper grounded conductor shall not be required to be insulated where it is: 1.1 In a raceway or part of a service cable assembly; 1.2 Directly buried in soil of suitable condition; or 1.2 Part of a cable assembly listed for direct burial without regard to soil conditions. 2. An aluminum or copper-clad aluminum grounded conductor shall not be required to be insulated where part of a cable or where identified for direct burial or utilization in underground raceways. [230.41 Exception].