§ 5-640 — International Residential Code—Section E3902.16 amended
Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 5-640
Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/00fea2bf-4274-41fd-acef-492277f4ead5
Sec. 5-640. - International Residential Code—Section E3902.16 amended.
Section E3902.16 of the 2018 International Residential Code is hereby amended to read as follows: E3902.16 Arc-fault circuit-interrupter protection. Branch-circuits that supply 120-volt, single-phase, 15- and 20-ampere outlets installed in bedrooms shall be protected by any of the following: [210.12(A)] 1. A listed combination-type arc-fault circuit-interrupter, installed to provide protection of the entire branch-circuit. [210.12(A)(1)] 2. A listed branch/feeder-type AFCI installed at the origin of the branch-circuit in combination with a listed outlet branch-circuit type arc-fault circuit-interrupter installed at the first outlet box on the branch-circuit. The first outlet box in the branch-circuit shall be marked to indicate that it is the first outlet of the circuit. [210.12(A)(2)] 3. A listed supplemental arc protection circuit breaker installed at the origin of the branch-circuit in combination with a listed outlet branch-circuit type arc-fault circuit-interrupter installed at the first outlet box on the branch-circuit where all of the following conditions are met: 3.1 The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit-interrupter. 3.2 The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 50 feet (15.2 m) for 14 AWG conductors and 70 feet (21.3 m) for 12 AWG conductors. 3.3 The first outlet box on the branch-circuit shall be marked to indicate that it is the first outlet on the circuit. [210.12(A)(3)] 4. A listed outlet branch-circuit type arc-fault circuit-interrupter installed at the first outlet on the branch-circuit in combination with a listed branch-circuit overcurrent protective device where all of the following conditions are met: 4.1 The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit-interrupter. 4.2 The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 50 feet (15.2 m) for 14 AWG conductors and 70 feet (21.3 m) for 12 AWG conductors. 4.3 The first outlet box on the branch-circuit shall be marked to indicate that it is the first outlet on the circuit. 4.4 The combination of the branch-circuit overcurrent device and outlet branch-circuit AFCI shall be identified as meeting the requirements for a system combination-type AFCI and shall be listed as such. [210.12(A)(4)] 5. Where metal outlet boxes and junction boxes and RMC, IMC, EMT, Type MC or steel-armored Type AC cables meeting the requirements of section E3908.8, metal wire ways or metal auxiliary gutters are installed for the portion of the branch-circuit between the branch-circuit overcurrent device and the first outlet, a listed outlet branch-circuit type AFCI installed at the first outlet shall be considered as providing protection for the remaining portion of the branch-circuit. [210.12(A)(5)] 6. Where a listed metal or nonmetallic conduit or tubing or Type MC cable is encased in not less than two inches (50.8 mm) of concrete for the portion of the branch-circuit between the branch-circuit overcurrent device and the first outlet, a listed outlet branch-circuit type AFCI installed at the first outlet shall be considered as providing protection for the remaining portion of the branch-circuit. [210.12(A)(6)]
(Code 2018, § 5-340)
Ask a question about Lawrence law
Corpus searches the Lawrence sections it holds and shows the ones that match, with their citations. Free, no sign-in.